- Article name
- Two-point controller
- Off-delay timer
- 0 min 40 s ±20% configurable via jumper
- Relay
- Changeover contact for ohm resistive load
- Capacity open contact
- 30 VDC / 5 A
- Capacity break contact
- 30 VDC / 3 A
- Fault clearance
- Closer with varistor VZ 05/390V
- Electrical Impedance
- 0…1/10/100 kΩ, configurable via plug-in jumpers
- Voltage/Current-input
- 0…1 V/10 V, 0(4)…20 mA, via jumpers configurable
- AC- Impedance input
- Serialimpedance:10…50 kΩ,Conductance: 30…10 µS
- Switchoutput
- SPDT relay (changer)
- Dimensions
- (LxWxH) 95 x 75 x 30 mm
- Weight
- 0.0648 kg
The PCB is designed with three different inputs which are linked internally and can be used separately or jointly for universal use. Our product range offers the suitable probes for this unit:
The dew formation probe SENSW-BTF to detect condensation, the humidity probe SENSW-RFF with sinter protection cap for regulation of the relative humidity and the conductivity probe SENSW-LWF for conductance evaluation. With the light probe SENSW-LIF the universal two-point controller can be used to automating Light switching on and off. The PCB controller accepts also most common industrial probes with 0…1 V/5 V/10 V, 0(4)…20 mA or 0...1k/10k/100k ohm outputs, making it a universal tool I a lot of applications.